CONDUCTOR ELECTRICO NH-80 2.5MM2 INDECO



Presentacion: UND (Unidad)
Cantidad / Stock: 0


PREFIERO CONSULTAR POR

Compartir

DESCRIPTION

Application:

Special application in places with poor ventilation, where, in case of fire, the emisión of corrosive, toxic gases and smoke threatens life and destroys electrical and electronic equipment, for example in residential buildings, offices, industrial plants, movie, theaters, discotheques, hospitals, airports, underground stations, etc. In case of fire, possible victims have higher chances of surviving because they don't breath in toxic gases and have good visibility to escape the area. They are usually installed in conduits and in indoor areas in tray. 100% purity copper, double layer, double protection. Not recommended for outdoor installations

Construction:

1. Conductor: Soft copper, class 2.

2. Insulation: Halogen free thermoplastic material HFFR, double layer.

Main characteristics:

Fire retardant, low emission dense smoke and halogen free.

Cross section:

From 1,5 mm2 up to 10 mm2.

Marking:

INDECO S.A. FREETOX NH-80 450/750 V - Section - Year - Sequential length.

Packing:

From 1,5 mm2  up to 6 mm2  in 100-meter standard coils.

10 mm2 in reels.

Colour:

At the customer's request.

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP 370.252: Thermoplastic and thermoset insulated cables of rated voltages up to and including 450/750 V.

NTP 370.266-3-31:Low voltage electrical cables. Cable with nominal voltage less tan or equal to 450/750 V - Part 3-31: Cables with special properties before the fire. Single core cables without cover with halogen-free thermoplastic insulation and low smoke emission.

NTP 370.264-7:Insulation, covering and coating materials for low voltage electrical power cables - Part 7: Halogen-free thermoplastic compounds for insulation.

International standards

IEC 60228: Conductors of insulated cables.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3:FT1 (Vertical-Specimen) Flame Test.

IEC 60332-3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C.

IEC 60684-2: Flexible insulating sleeving - Part 2: Methods of test.

IEC 60754-1: Test on gases evolved during combustion of materials from cables – Part 1: Determination of the halogen acid gas content.

IEC 60754-2: Test on gases evolved during combustion of materials from cables – Part 2: Determination of acidity (by pH measurement) and conductivity.

IEC 61034-2: Measurement of smoke density of cables burning under defined conditions.

CHARACTERISTICS

Construction characteristics

Conductor material: Soft copper

Insulation: Halogen free thermoplastic material

Halogen: free IEC 60754-1

Conductor flexibility: Class 2 IEC 60228

Conductor shape: Compressed

Electrical characteristics

Rated Voltage Uo/U (Um): 450 / 750 V

Dielectric strength: 2.5 kV

Time of application Dielectric strength core to screen: AC 5 min.

Usage characteristics

Gases toxicity: Low toxicity to IEC 60684-2

Gases corrosivity: Low pH Corrosivity IEC 60754-2

Smoke density: Low IEC 61034-2

Flame retardant: IEC 60332-1-2; FT1

Fire retardant: IEC 60332-3-24 Cat.C

Minimum operating temperature: -40 °C

Maximum operating temperature: 80 °C

Overload maximum core temperature: 100 °C

Short-circuit max. conductor temperature: 160 °C

 